产品概述科华不间断电源 YTR11-J 系列为 19 英寸机架式双变换在线式 UPS,覆盖 1kVA~10kVA 功率段,依托全数字 DSP 三电平高频变换技术打造,是中小型机房、精密仪器、智能设备专用供电保护设备。科华 UPS 电源 兼顾节能、高带载、智能运维多重优势,整机满载效率*高可达 95%,远超行业同类产品;同时兼容铅酸外置电池包、长寿命磷酸铁锂电池两种储能方案,电网适应性极强,可适配发
| 参数项目(中文) | Parameter Item(English) | YTR1101-J | YTR1101L-J | YTR1102L-J | YTR1103L-J | YTR1106L-J | YTR1110-J |
|---|---|---|---|---|---|---|---|
| 产品型号 | Model | YTR1101-J | YTR1101L-J | YTR1102L-J | YTR1103L-J | YTR1106L-J | YTR1110-J |
| 输入制式 | Input System | 单相三线 Single-phase three-wire | 单相三线 Single-phase three-wire | 单相三线 Single-phase three-wire | 单相三线 Single-phase three-wire | 单相三线 Single-phase three-wire | 单相三线 Single-phase three-wire |
| 输入电压范围 (Vac) | Input Voltage Range | 110~300 | 80~275 | 80~275 | 80~275 | 80~275 | 80~275 |
| 输入频率范围 (Hz) | Input Frequency Range | 40~70,50/60Hz 自适应 40~70, 50/60Hz auto-adaptive | 40~70,50/60Hz 自适应 40~70, 50/60Hz auto-adaptive | 40~70,50/60Hz 自适应 40~70, 50/60Hz auto-adaptive | 40~70,50/60Hz 自适应 40~70, 50/60Hz auto-adaptive | 40~70,50/60Hz 自适应 40~70, 50/60Hz auto-adaptive | 40~70,50/60Hz 自适应 40~70, 50/60Hz auto-adaptive |
| 旁路同步跟踪范围 | Bypass Synchronization Tracking Range | ±10% | ±10% | ±10% | ±10% | ±10% | ±10% |
| 旁路输入电压范围 (Vac) | Bypass Input Voltage Range | 208/220/230/240±1% | 208/220/230/240±1% | 208/220/230/240±1% | 208/220/230/240±1% | 208/220/230/240±1% | 208/220/230/240±1% |
| 输入功率因数 | Input Power Factor | >0.99(线性满载) >0.99 (Linear full load) | >0.99(线性满载) >0.99 (Linear full load) | >0.99(线性满载) >0.99 (Linear full load) | >0.99(线性满载) >0.99 (Linear full load) | >0.99(线性满载) >0.99 (Linear full load) | >0.99(线性满载) >0.99 (Linear full load) |
| 输入电流谐波 THDi | Input Current Harmonic THDi | <5%(线性满载) <5% (Linear full load) | <5%(线性满载) <5% (Linear full load) | <5%(线性满载) <5% (Linear full load) | <5%(线性满载) <5% (Linear full load) | <5%(线性满载) <5% (Linear full load) | <5%(线性满载) <5% (Linear full load) |
| 电池电压 (Vdc) | Battery Voltage | 24V | 36V | 72V | 72V | 默认 192V(192~240V 软件可调) Default 192V (192~240V adjustable by software) | 默认 192V(192~240V 软件可调) Default 192V (192~240V adjustable by software) |
| 输出功率因数 | Output Power Factor | 0.8(30℃以下可长期 0.9 带载) 0.8 (0.9 long-term load below 30℃) | 0.8(30℃以下可长期 0.9 带载) 0.8 (0.9 long-term load below 30℃) | 0.8(30℃以下可长期 0.9 带载) 0.8 (0.9 long-term load below 30℃) | 0.8(30℃以下可长期 0.9 带载) 0.8 (0.9 long-term load below 30℃) | 0.9(30℃以下可长期 1.0 带载) 0.9 (1.0 long-term load below 30℃) | 0.9(30℃以下可长期 1.0 带载) 0.9 (1.0 long-term load below 30℃) |
| 输出电压 (Vac) | Output Voltage | 默认 220V,可选 208/220/230/240±1% Default 220V, optional 208/220/230/240±1% | 默认 220V,可选 208/220/230/240±1% Default 220V, optional 208/220/230/240±1% | 默认 220V,可选 208/220/230/240±1% Default 220V, optional 208/220/230/240±1% | 默认 220V,可选 208/220/230/240±1% Default 220V, optional 208/220/230/240±1% | 默认 220V,可选 208/220/230/240±1% Default 220V, optional 208/220/230/240±1% | 默认 220V,可选 208/220/230/240±1% Default 220V, optional 208/220/230/240±1% |
| 输出频率 (Hz) | Output Frequency | 同步模式:50/60±10%;自振模式:50/60±0.2% Sync mode:50/60±10%; Free-run mode:50/60±0.2% | 同步模式:50/60±10%;自振模式:50/60±0.2% Sync mode:50/60±10%; Free-run mode:50/60±0.2% | 同步模式:50/60±10%;自振模式:50/60±0.2% Sync mode:50/60±10%; Free-run mode:50/60±0.2% | 同步模式:50/60±10%;自振模式:50/60±0.2% Sync mode:50/60±10%; Free-run mode:50/60±0.2% | 同步模式:50/60±10%;自振模式:50/60±0.2% Sync mode:50/60±10%; Free-run mode:50/60±0.2% | 同步模式:50/60±10%;自振模式:50/60±0.2% Sync mode:50/60±10%; Free-run mode:50/60±0.2% |
| 波形失真度 THDv | Waveform Distortion THDv | 线性负载<2%;非线性负载<5% Linear load<2%, Non-linear load<5% | 线性负载<2%;非线性负载<5% Linear load<2%, Non-linear load<5% | 线性负载<2%;非线性负载<5% Linear load<2%, Non-linear load<5% | 线性负载<2%;非线性负载<5% Linear load<2%, Non-linear load<5% | 线性负载<2%;非线性负载<3% Linear load<2%, Non-linear load<3% | 线性负载<2%;非线性负载<3% Linear load<2%, Non-linear load<3% |
| 整机效率 | Overall Efficiency | *高 95% Max 95% | *高 95% Max 95% | *高 95% Max 95% | *高 95% Max 95% | *高 95% Max 95% | *高 95% Max 95% |
| 逆变过载能力 | Inverter Overload Capacity | 115%~130% 过载维持 1min;130%~150% 维持 1s;>150% 仅 200ms 115%~130%:1min;130%~150%:1s;>150%:200ms | 115%~130% 过载维持 1min;130%~150% 维持 1s;>150% 仅 200ms 115%~130%:1min;130%~150%:1s;>150%:200ms | 115%~130% 过载维持 1min;130%~150% 维持 1s;>150% 仅 200ms 115%~130%:1min;130%~150%:1s;>150%:200ms | 115%~130% 过载维持 1min;130%~150% 维持 1s;>150% 仅 200ms 115%~130%:1min;130%~150%:1s;>150%:200ms | 115%~130% 过载维持 10min;130%~150% 维持 30s;>150% 仅 500ms 115%~130%:10min;130%~150%:30s;>150%:500ms | 115%~130% 过载维持 10min;130%~150% 维持 30s;>150% 仅 500ms 115%~130%:10min;130%~150%:30s;>150%:500ms |
| 直流启动功能 | DC Cold Start Function | ✅具备 Support | ✅具备 Support | ✅具备 Support | ✅具备 Support | ✅具备 Support | ✅具备 Support |
| 通信功能 | Communication Port | 标配 RS232、EPO;可选 USB、SNMP、RS485 干接点、协议转换卡 Standard:RS232,EPO; Optional:USB/SNMP/RS485 relay card | 标配 RS485、EPO;可选 USB、SNMP、RS485 干接点、协议转换卡 Standard:RS485,EPO; Optional:USB/SNMP/relay card | 标配 RS485、EPO;可选 USB、SNMP、RS485 干接点、协议转换卡 Standard:RS485,EPO; Optional:USB/SNMP/relay card | 标配 RS485、EPO;可选 USB、SNMP、RS485 干接点、协议转换卡 Standard:RS485,EPO; Optional:USB/SNMP/relay card | 标配 RS485、EPO;可选 USB、SNMP、RS485 干接点、协议转换卡 Standard:RS485,EPO; Optional:USB/SNMP/relay card | 标配 RS485、EPO;可选 USB、SNMP、RS485 干接点、协议转换卡 Standard:RS485,EPO; Optional:USB/SNMP/relay card |
| 选配件 | Optional Accessories | B2U-36 系列 36V 铅酸电池包、磷酸铁锂模组、SNMP 卡、RS485 干接点、USB 卡、19 英寸标准机柜、PDU、设备导轨 | B2U-36/B2U-72/B3U-72 系列外置电池包、磷酸铁锂储能模组、各类通信扩展卡、服务器机柜、层板、理线配件 | B2U-72/B3U-72 外置电池包、锂电模组、监控通讯卡、机柜辅件 | B2U-72/B3U-72 外置电池包、锂电模组、监控通讯卡、机柜辅件 | B3U-192 铅酸电池包、长寿命磷酸铁锂模块、远程监控卡、19 寸机柜、承重导轨 | B3U-192 铅酸电池包、长寿命磷酸铁锂模块、远程监控卡、19 寸机柜、承重导轨 |
| 报警功能 | Alarm Function | 电池低压、市电异常、UPS 故障、输出过载 Battery low voltage, mains abnormal, UPS fault, output overload | 电池低压、市电异常、UPS 故障、输出过载 Battery low voltage, mains abnormal, UPS fault, output overload | 电池低压、市电异常、UPS 故障、输出过载 Battery low voltage, mains abnormal, UPS fault, output overload | 电池低压、市电异常、UPS 故障、输出过载 Battery low voltage, mains abnormal, UPS fault, output overload | 电池低压、市电异常、UPS 故障、输出过载 Battery low voltage, mains abnormal, UPS fault, output overload | 电池低压、市电异常、UPS 故障、输出过载 Battery low voltage, mains abnormal, UPS fault, output overload |
| 噪音 (dB) | Noise Level | <45 | <45 | <50 | <50 | <55 | <55 |
| 工作温度 (℃) | Operating Temperature | -5 ~ 40 | -5 ~ 40 | -5 ~ 40 | -5 ~ 40 | -5 ~ 40 | -5 ~ 40 |
| 环境湿度 | Ambient Humidity | 0~95%,无冷凝 0~95%, non-condensing | 0~95%,无冷凝 0~95%, non-condensing | 0~95%,无冷凝 0~95%, non-condensing | 0~95%,无冷凝 0~95%, non-condensing | 0~95%,无冷凝 0~95%, non-condensing | 0~95%,无冷凝 0~95%, non-condensing |
| 尺寸 (宽 × 深 × 高 mm) | Dimension(W×D×H) | 438×413×86(2U) | 438×413×86(2U) | 438×413×86(2U) | 438×413×86(2U) | 438×500×86(2U) | 438×500×86(2U) |
| 净重 (kg) | Net Weight | 10.3 | 6.5 | 8.8 | 8.8 | 10.6 | 12.2 |
科华不间断电源 节能优势突出:整机满载效率*高 95%,以 10kW 负载 24h 运行测算,相较行业 92% 平均水平每日节电 7.2 度,全年可节约电费超 1700 元,长期使用大幅降低机房运营电费。
科华 UPS 电源 储能方案灵活:内置机型自带电池,长机可外接 36/72/192V 标准化电池包,支持多组并联扩容备电时长;同时兼容磷酸铁锂模组,锂电体积、重量仅铅酸电池 1/3,循环寿命 5000 次,整机 15 年无需更换储能单元。
科华 UPS 电源 运维便捷安全:搭载蓝屏广角 LCD 显示屏,实时展示电压、电池容量、设备温度;风机动态调速降噪,长机电池包支持热插拔,更换电池不中断后端负载供电;具备 EPO 紧急关机、完整过载 / 短路 / 过温多重防护,适配机房 7×24 小时不间断运行场景。
电网适配与兼容性:全系列输入电压区间极宽,小功率机型支持 110~300Vac 输入,大功率机型*低可承受 80Vac 低压输入,*适配发电机供电;输入功率因数>0.99、谐波 THDi<5%,不会反向污染电网,适合广电、通信、实验室精密仪器供电保护。
机架一体化配套:可搭配科华原厂 19 英寸标准服务器机柜、竖装防雷 PDU、承重导轨、封板等辅件,整套供电系统统一兼容,线缆管理、散热布局标准化,快速搭建小型数据中心供电体系。